EasyManua.ls Logo

Parker AC30 series - Page 275

Parker AC30 series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Reference C-93
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
DC Inj Timeout
0330
Parameters::Motor Control::Inj Braking
90.000
0.000 to 600.000
s
ALWAYS
Maximum time in the low frequency injection braking state
DC Inj Base Volts
0331
Parameters::Motor Control::Inj Braking
100.00
0.00 to 115.47
%
ALWAYS
Maximum volts applied at base speed
Note: DC injection braking procedure has higher percentage of successful stoppages for the lower power range (frames D-G), than at higher power
range (frames H-K).

Table of Contents

Other manuals for Parker AC30 series

Related product manuals