C-104 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Anin 01 Value
0039
Same as PNO 38
x.x
-100.0 to 100.0
%
NEVER
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
Anin 01 Break
0040
Same as PNO 38
NEVER
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to FALSE.
Anin 02 Value
0041
Same as PNO 38
x.x
-100.0 to 100.0
%
NEVER
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the hardware
range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
Anout 01 Value
0042
Same as PNO 38
0.00
Min to Max
%
ALWAYS
Terminal X11.3
The desired output value expressed as a percentage of the output range.
Range
Mapping
0..10V
0% gives 0V, 100% gives 10V
0..20MA
0% gives 0mA, 100% gives 20mA
4..20MA
0% gives 4mA, 100% gives 20mA
Anout 02 Value
0043
Same as PNO 38
0.00
Min to Max
%
ALWAYS
Terminal X11.4
The desired output value expressed as a percentage of the output range.
Range
Mapping
-10..10V
-100% gives -10V, 100% gives 10V
0..10V
0% gives 0V, 100% gives 10V