Parameter Reference C-173
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Time Since Power-On
1733
Parameters::Device
Manager::Runtime Statistics
0.000 to Max
s
NEVER
The time in seconds since power was applied to the control module, (either 24v or 3-phase power).
Functional Description
The Runtime Statistics group of parameters indicate the working age of the drive. The Control Board Up Time value is used as a reference when
recording the time at which a trip occurs. Similarly, the HV SMPS Up Time is used as a reference when recording the time at which a disabled trip
event occurs when the drive is operating in Fire Mode, (see Chapter 13: Fire Mode, and HA502134U002 “Fan Control Application manual).