Parameter Reference C-191
AC30 series Variable Speed Drive
Status Word
0661
Parameters::Motor Control::Sequencing
0:READY TO SWITCH ON
1:SWITCHED ON
2:OPERATION ENABLED
3:FAULTED
4:VOLTAGE ENABLED
5:QUICKSTOP INACTIVE
6:SWITCH ON DISABLED
9:CONTROL FROM COMMS
12:JOG OPERATION
13:REVERSE OPERATION
14:REFERENCE FROM
COMMS
15:STOPPING
NEVER
This is the DS402 Status Word
Sequencing State
0678
Parameters::Motor Control::Sequencing
0:NOT READY TO SWITCH ON
1:SWITCH ON DISABLED
2:READY TO SWITCH ON
3:SWITCHED ON
4:OPERATION ENABLED
5:QUICKSTOP ACTIVE
6:FAULT REACTION ACTIVE
7:FAULTED
s
NEVER
Drive DS402 Sequencing State.
Switch On Timeout
0679
Parameters::Motor Control::Sequencing
0.000
0.000 to 100.000
s
ALWAYS
Time allowed for line contactor to close when entering the Switched On state from Switched Off state. If this time is non-zero, a Line
Contactor trip will occur if the DC Link Voltage remains low until the timeout expires. If the timeout is set to zero, an Under Voltage trip
will occur immediately.
App Reference
0680
Parameters::Motor Control::Sequencing
0.00
-110.00 to 110.00
%
ALWAYS
Reference from terminals (via. the application)