EasyManua.ls Logo

Parker AC30 series - Page 438

Parker AC30 series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-256 Parameter Reference
AC30 series Variable Speed Drive
1409
Warranty Trips Record.01 OVER VOLTAGE
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03345
1411
Warranty Trips Record.03 OVER CURRENT
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03349
1412
Warranty Trips Record.04 STACK FAULT
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03351
1413
Warranty Trips Record.05 STACK OVER CURRENT
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03353
1416
Warranty Trips Record.08 INVERSE TIME
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03359
1419
Warranty Trips Record.11 HEATSINK OVERTEMP
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03365
1420
Warranty Trips Record.12 INTERNAL OVERTEMP
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03367
1423
Warranty Trips Record.15 BRAKE SHORT CCT
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03373
1425
Warranty Trips Record.17 BRAKE SWITCH
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03377
1430
Warranty Trips Record.22 VDC RIPPLE
Parameters::Trips::Trips History
BOOL
NEVER
ENGINEER
1
03387
1441
Anout 01 ABS
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO Configure
BOOL
FALSE
ALWAYS
OPERATOR
4
03409
1442
Recent Trip Times
Parameters::Trips::Trips History
ARRAY[0..9]
NEVER
OPERATOR
03411
1443
Recent Trip Times[0]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03413
1444
Recent Trip Times[1]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03415
1445
Recent Trip Times[2]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03417
1446
Recent Trip Times[3]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03419
1447
Recent Trip Times[4]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03421
1448
Recent Trip Times[5]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03423
1449
Recent Trip Times[6]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03425
1450
Recent Trip Times[7]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03427
1451
Recent Trip Times[8]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03429
1452
Recent Trip Times[9]
Parameters::Trips::Trips History
UDINT
0 to Max
s
NEVER
OPERATOR
1
03431
1458
Modbus Conn Timeout
Parameters::Base Comms::Modbus
TIME
66.000
0.000 to 100000.000
s
ALWAYS
TECHNICIAN
03443
1459
Max Spd when Autotuned
Parameters::Motor Control::Autotune
REAL
x.
-1 to 100000
RPM
NEVER
ENGINEER
3,6,9,4
03445
1460
Anout 02 Scale
Same as PNO 1441
REAL
1.0000
Min to Max
ALWAYS
OPERATOR
03447
1461
Anin 11 Offset
Setup::Inputs and Outputs::Option
Parameters::Option IO::General Purpose IO
REAL
0.00
Min to Max
%
ALWAYS
OPERATOR
4
03449
1462
Anin 11 Scale
Same as PNO 1461
REAL
1.0000
Min to Max
ALWAYS
OPERATOR
4
03451
1463
Anin 12 Offset
Same as PNO 1461
REAL
0.00
Min to Max
%
ALWAYS
OPERATOR
4
03453
1464
Anin 12 Scale
Same as PNO 1461
REAL
1.0000
Min to Max
ALWAYS
OPERATOR
4
03455
1465
Anin 13 Offset
Same as PNO 1461
REAL
0.00
Min to Max
%
ALWAYS
OPERATOR
4
03457
1466
Anin 13 Scale
Same as PNO 1461
REAL
1.0000
Min to Max
ALWAYS
OPERATOR
4
03459
1467
Anout 02 Offset
Same as PNO 1441
REAL
0.00
Min to Max
%
ALWAYS
OPERATOR
03461
1468
Anout 02 ABS
Same as PNO 1441
BOOL
FALSE
ALWAYS
OPERATOR
03463
1469
AR Enable
Setup::Motor Control::Auto Restart
Parameters::Motor Control::Auto Restart
BOOL
FALSE
ALWAYS
OPERATOR
03465
1470
AR Mode
Same as PNO 1469
USINT
(enum)
1
0:TRIP RESET
1:AUTO RESTART
2:AUTO START
ALWAYS
OPERATOR
03467
1471
AR Max Restarts
Same as PNO 1469
USINT
10
1 to 20
ALWAYS
OPERATOR
03469
1472
AR Trip Mask
Same as PNO 1469
DWORD
(bitfield)
FFFFFFFF
0:01 OVER VOLTAGE
1:02 UNDER VOLTAGE
2:03 OVER CURRENT
3:04 STACK FAULT
4:05 STACK OVER CURRENT
5:06 CURRENT LIMIT
6:07 MOTOR STALL
7:08 INVERSE TIME
8:09 MOTOR I2T
9:10 LOW SPEED I
10:11 HEATSINK OVERTEMP
11:12 INTERNAL OVERTEMP
12:13 MOTOR OVERTEMP
13:14 EXTERNAL TRIP
14:15 BRAKE SHORT CCT
15:16 BRAKE RESISTOR
16:17 BRAKE SWITCH
17:18 LOCAL CONTROL
18:19 COMMS BREAK
19:20 LINE CONTACTOR
20:21 PHASE FAIL
21:22 VDC RIPPLE
22:23 BASE MODBUS BREAK
23:24 24 V OVERLOAD
24:25 PMAC SPEED ERROR
25:26 OVERSPEED
26:27 STO ACTIVE
27:28 FEEDBACK MISSING
ALWAYS
TECHNICIAN
03471