7-16 Trips & Fault Finding
AC30 series Variable Speed Inverter
The data recorded at the instant of the trip is output at the end of the file. This consists of:
Control module serial number, (parameter 0977 Control Module Serial)
Time of the trip. This is either the control board age, or the time from the optional Real Time Clock if fitted.
State of all other trips, active or warning.
Count of total motor starts, (parameter 1732 Motor Start Count)
Count of total times the 3-phase has been powered
For each trip, a count of the total times that trip has been activated.
A record of near trip events for Over Current, Over Voltage and Under Voltage.
The product code of the drive, expressed as a number in internal format.
The IO Option fitted, (parameter 1179 Option IO Fitted)
The Communications Option fitted, (parameter 0045 Comms Fitted)
The System board type, (parameter 1740 System Board Fitted)
The motor control type, (parameter 0511 Motor Type or AFE)
The control strategy, (parameter 0512 Control Stragegy)
The control type, (parameter 1533 Control Type)
The firmware version
The version of CoDeSys used to create the application.