PSRmodular system
184 / 232
PHOENIX CONTACT 109241_en_03
Blind Time Only for “Muting Closing” with “CURTAIN” (electro-sensitive protective equipment):
The “Blind Time” parameter should be activated if, at the end of the muting cycle, objects
may protrude which occupy the light grid and set “I
NPUT” to logic “0” (e.g., material protrud-
ing from a pallet, etc.). During the “Blind Time”, “I
NPUT” remains at logic “1”. The “Blind Time”
can be parameterized between 250 ms and 1 s.
CURTAIN (electro-sensitive protective equipment)
Se-
quence
S1 S2 INPUT S3 S4 MUTING
1st 0 0 1 0 0 0
2nd 1 0 1 0 0 0
3rd 1 1 1 0 0 1
Muting
active
4th 1 1 0/1 0 0 1
5th 1 1 0/1 1 0 1
6th 1 1 0/1 1 1 1
7th 0 1 0/1 1 1 1
8th 0 0 0 1 1 1
9th 0 0 1 1 1 0
10th 0 0 1 0 1 0
11th 0 0 1 0 0 0
SENSOR
Se-
quence
S1 S2 INPUT S3 S4 MUTING
1st 0 0 1 0 0 0
2nd 1 0 1 0 0 0
3rd 1 1 1 0 0 1
Muting
active
4th 1 1 0/1 0 0 1
5th 1 1 0/1 1 0 1
6th 1 1 0/1 1 1 1
7th 0 1 0/1 1 1 1
8th 0 0 0 1 1 1
9th 0 0 1 1 1 1
10th 0 0 1 0 1 0
11th 0 0 1 0 0 0