4.4 Basic Parameter Adjustments
138 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Note: 1. After entering a stop command, the drive will not accept another run command until the
time set to L2-03 (Minimum Baseblock Time) passes.
2. Do not enter another run command until the motor comes to a complete stop. If a run
command must be entered before the motor has fully stopped, use DC Injection or Speed
Search functions to slow the motor or catch the motor before restarting.
DC Injection Braking to Stop (b1-03 = 2)
DC Injection braking can be used to eliminate motor from coasting when the drive
reaches the minimum output frequency during a stop. This feature allows the drive
to stop the motor faster than coasting freely to a stop without allowing regenerative
energy to develop.
This stopping method applies DC current to the motor windings and thereby stops
the motor without operating in the regenerative mode. When the stop command is
input, the drive waits the time set in L2-03 (Minimum Base Block time) and then
applies the DC current level set in b2-02. The time for which DC braking is applied
is determined by the output frequency at the time of the stop command as shown in
Figure 4.19.
When b1-03 = 2, the actual DC injection time is calculated as follows:
(b2-04) x 10 x (Output frequency) / (E1-04)
Note: DC Injection braking cannot be selected as a stopping method in PM Open Loop
Vector Control.

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled