EasyManuals Logo

YASKAWA V1000 Series Installation & Start-Up Manual

YASKAWA V1000 Series
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #158 background imageLoading...
Page #158 background image
4.4 Basic Parameter Adjustments
158 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Notes on Motor Protection
Motor protection meeting UL and cUL standards has been achieved with the
motor overload protection time (L1-02) set to factory default setting. Therefore,
this parameter does not normally need to be changed. In the event the motor
overload characteristics are known, the overload time can be adjusted to more
closely match the motor. To detect overload more quickly, reduce L1-02.
2
Inverter
Duty motor
(10:1)
Motor designed for
effective cooling above
6 Hz.
Continuous operation
between 6 and 60 Hz.
3
Vector
motor
(1000:1)
Motor capable of
effective cooling at
extremely low speeds
(0.6 Hz).
Continuous operation
between 0 and 60 Hz.
A: Typical maximum speed for Yaskawa motor frame number 200LJ and greater
B: Typical maximum speed for Yaskawa motor frame numbers 160MJ – 180LJ
C: Typical maximum speed for Yaskawa motor frame number 132MHJ or less
D: Typical maximum speed for Yaskawa motor frame number 132MJ or less
L1-01
Setting
Motor
Type
Overload Tolerance Cooling Fan Capacity
Electrothermal
Protection
(100% motor
overload)
100
150
55
50
(%)
60 seconds
Continuous
0
110
100
(60Hz)
120 167 200
(%)
Speed
A
D
B
Rated Speed = 100% Speed
Torque
100
150
90
50
Torque
(%)
0
1
60 seconds
Rated Speed = 100% Speed
100
(60Hz)
120
167 200
(%)
Speed
Continuous
A
B
D

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled