EasyManuals Logo

YASKAWA V1000 Series Installation & Start-Up Manual

YASKAWA V1000 Series
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #371 background imageLoading...
Page #371 background image
B.2 Parameter Table
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07) 371
Parameter List
B
1B Program Lockout
Open: Only the frequency reference monitor (U1-01)
may be saved.
Closed: Parameters may be edited and saved.
OOO
1E Reference Sample Hold
Closed: Samples the analog frequency reference and
operates the drive at that speed.
OOO
20 to
2F
External Fault (user selection
possible)
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue
running)
2D: N.C., Always Detected, Alarm Only (continue
running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
OOO
30 PID Integral Reset
Closed: Resets the PID control integral value.
A stop command was entered during PID control or PID
was reset while the drive was stopped.
OOO
31 PID Integral Hold
Closed: Maintains the current level of the PID control
integral.
OOO
32 Multi-Step Speed Reference 4
The values set to d1-01 through d1-16 can be selected
using a combination of multi-step speed reference 1
through 4.
OOO
34 PID Soft Starter Closed: Disregards b5-17. O O O
35 PID Input Switch Closed: Reverses the PID fault signal (1 to -1 or -1 to 1) O O O
40
Forward Run Command
(2-wire sequence)
Open: Stop
Closed: Forward run
Note: Settings 42 and 43 cannot be utilized at the same
time.
OOO
41
Reverse Run Command
(2-wire sequence)
Open: Stop
Closed: Reverse run
Determines direction only. Simply switching this signal
on or off does not issue a run command.
Settings 42 and 43 cannot be used at the same time.
OOO
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description
Control
Mode
Pg.
V/
f
O
LV
P
M

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled

Related product manuals