B.2 Parameter Table
380 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
H5-04
Stopping Method
After Communication
Error
Selects the stopping method when a
communication time-out fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
0 to 3 3 AAA 428
H5-05
Communication Fault
Detection Selection
Enables or disables the communications time-
out fault (CE).
0: Disabled - A communication loss will not
cause a communication fault.
1: Enabled - If communication is lost for more
than two seconds, a CE fault will occur.
0,1 1 A A A 429
H5-06
Drive Transmit Wait
Time
Set the delay time from when the drive
receives data to when the drive sends data.
5 to 65 5 ms A A A 42A
H5-07
RTS Control
Selection
Enables or disables "request to send" (RTS)
control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
0,1 1 AAA 42B
H5-09 CE Detection Time
Sets the time required to detect a
communications error. Adjustment may be
need when networking several drives.
0.0 to
10.0 s
2.0 s A A A 435
H5-10
Unit Selection for
MEMOBUS/Modbus
Register 0025H
Selects the units used for MEMOBUS/Modbus
registry 0025H (Output Voltage Reference
Monitor).
0: 0.1 V units
1: 1 V units
0, 1 0 A A A 436
H5-11
Communications
ENTER Function
Selection
Select the function for the enter command that
saves parameter data to the drive.
0: Save parameter data that was edited to the
drive when the enter command is given.
1: Parameter data that has been edited is saved
when the enter command is given (compatible
with the V7).
0, 1 1 A A A 43C
H5-12
Run Command
Method Selection
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
0, 1 0 A A A 43D
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled

Related product manuals