B.2 Parameter Table
402 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
o2-03
User Parameter
Default Value
Allows storing of parameter settings as a User
Initialization Selection.
0: No Change
1: Set Defaults - Saves current parameter
settings as user initialization.
2: Clear All - Clears the currently saved user
initialization.
0 to 2 0 A A A 507 —
o2-04 Drive/kVA Selection
Sets the kVA of the drive.
This parameter only needs to be set when
installing a new control board. Do not change
for other reason.
0 to FF
<12> AAA 508 —
o2-05
Frequency Reference
Setting Method
Selection
Sets the function of the Data/Enter key.
0: Disabled - Data/Enter key must be pressed
to enter a frequency reference.
1: Enabled - Data/Enter key is not required.
The frequency reference is adjusted by the
“up” and “down” arrow keys on the digital
operator without having to press the ENTER
key.
0,1 0 A A A 509 —
o2-06
Operation Selection
when Digital
Operator is
Disconnected
Sets drive action when the digital operator is
removed in Local mode or with b1-02 = 0.
0: Disabled - The drive will not stop when the
digital operator is removed.
1: Enabled - The drive will fault (OPR) and
coast to stop when the digital operator is
removed.
0,1
<14> AAA 50A —
o2-07
Motor Direction at
Power Up when
Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be
assigned to the digital operator.
0 to 1 0 A A A 527 —
o2-09
Initialization
Specification
Selection
DELETE for U.S.
Sets parameter default values after a drive
initialization (A1-03) is executed.
1: American specification
2: European specification
3: China specification
0 to 4 0
A
F
A
F
A
F
50D —