TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01 3-27
Monday, November 26, 2001 1:09 pm
Trigger Output
Trigger Output enables the user to operate a circuit breaker using an
input generated by the TDR9000, as connected through the Trigger Out
connectors of the System module. The pulse width can be set, along with
a trigger delay. The Trigger Output parameters pertain to only one thing:
the TDR9000 Trigger Out channel (on the System module). The Trigger
Output is essentially a solid state switch output (dry contact), that can be
used to control an accessory, or trigger another TDR9000. The Trigger
can operate in circuits up to 300 V peak, 0.5 A maximum.
There are two Trigger State conditions:
•Off
•On
The following fields are active when the Trigger State is On:
• Pulse Width
• Trigger Delay
• Polarity