Configuration
112 UDC3500 Universal Digital Controller Product Manual 3/07
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
RLYSTAT2
1OF2OF
1ON2OF
1OF2ON
1ON2ON
DIGITAL OUTPUT STATUS AT 0 % OUTPUT FOR
LOOP 2—Allows the following selections:
1OF2OF Output 1 de-energized
Output 2 de-energized
1ON2OF Output 1 energized
Output 2 de-energized
1OF2ON Output 1 de-energized
Output 2 energized
1ON2ON Output 1 energized
Output 2 energized
CUR OUT1
FIRST CURRENT OUTPUT—If the First Current
Output is not used to perform one of the above
output algorithms, it may be used to perform an
Auxiliary Output function. This prompt will not show
up when the First Current Output is used in one of
the above output algorithms.
DISABLE
NO FIRST CURRENT OUTPUT—Current Output
disabled and output set to 0 mA.
INPUT 1
INPUT 1—This represents the configured range of
Input 1.
FOR EXAMPLE:
Input 1 Type = J Thermocouple (0 °F to 1600 °F)
First Current Output Low Scale Value = 0.0
First Current Output High Scale Value = 1600
C1 Range = 4-20 mA
Then:
0 °F display = 0 % output (4 mA)
800 °F display = 50 % output (12 mA)
1600 °F display = 100 % output (20 mA)
INPUT 2
INPUT 2—Same as Input 1.
INPUT 3
INPUT 3—Same as Input 1.
ATTENTION Do not configure Input 3 when input 3
is used for slidewire or slidewire emulation.
INPUT 4
INPUT 4—Same as Input 1.
INPUT 5
INPUT 5—Same as Input 1.