Configuration
116 UDC3500 Universal Digital Controller Product Manual 3/07
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
LOW VAL
Low Scale Value within
the range of the selected
variable to represent the
minimum output (0 or 4
mA)
CURRENT OUTPUT LOW SCALING FACTOR
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
HIGH VAL
High Scale Value within
the range of the selected
variable to represent the
maximum output (20 mA)
CURRENT OUTPUT HIGH SCALING FACTOR
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.