Configuration 
116  UDC3500 Universal Digital Controller Product Manual  3/07 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
LOW VAL 
Low Scale Value within 
the range of the selected 
variable to represent the 
minimum output (0 or 4 
mA) 
CURRENT OUTPUT LOW SCALING FACTOR—
Used only when CUR OUT is any selection other 
than DISABLE. This is a value in engineering units 
used to represent all CUR OUT parameters except 
Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %. However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
HIGH VAL 
High Scale Value within 
the range of the selected 
variable to represent the 
maximum output (20 mA) 
CURRENT OUTPUT HIGH SCALING FACTOR—
Used only when CUR OUT is any selection other 
than DISABLE. This is a value in engineering units 
used to represent all CUR OUT parameters except 
Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %. However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %.