Configuration
3/07 UDC3500 Universal Digital Controller Product Manual 139
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
OUT RATE
ENABLE
DISABLE
OUTPUT CHANGE RATE—Enables or disables the
Output Change Rate. The maximum rate is set at
prompt PCT/M UP or PCT/M DN. Only available for
PID-A, PID-B, PD+MR control algorithms.
ENABLE—Allows output rate.
DISABLE—Disables output rate.
PCT/M UP
0 to 9999 % per minute
OUTPUT RATE UP VALUE—This selection limits
the rate at which the output can change upward.
Enter a value in percent per minute. Appears only if
OUT RATE is enabled. “0” means no output rate
applied.
PCT/M DN
0 to 9999 % per minute
OUTPUT RATE DOWN VALUE—This selection
limits the rate at which the output can change
downward. Enter a value in percent per minute.
Appears only if OUT RATE is enabled. “0” means no
output rate.
OUTHiLIM
HIGH OUTPUT LIMIT—This is the highest value of
output beyond which you do not want the controller
automatic output to exceed.
0 % to 100 %
–5 % to 105 %
For relay output types.
For current output types
OUTLoLIM
LOW OUTPUT LIMIT—This is the lowest value of
output below which you do not want the controller
automatic output to exceed.
0 % to 100 %
–5 % to 105 %
For relay output types.
For current output types
I Hi LIM
(Note 4)
Within the range of the
output limits
HIGH RESET LIMIT—This is the highest value of
output beyond which you do not want reset action to
occur
I Lo LIM
(Note 4)
Within the range of the
output limits
LOW RESET LIMIT—This is the lowest value of
output beyond which you do not want reset action to
occur.
DROPOFF
(Note 4)
–5 to 105 % of output
CONTROLLER DROPOFF VALUE—Output value
below which the controller output will drop off to the
low output limit value set in prompt OUTLoLIM.
DEADBAND
DEADBAND—An adjustable gap between the
operating ranges of output 1 and output 2 in which
neither output operates (positive value) or both
outputs operate (negative value).
–5.0 to 25.0 %
0.0 to 25.0 %
0.5 to 5.0 %
Time Duplex
On-Off Duplex
Position Proportional and Three Position Step