Configuration 
148  UDC3500 Universal Digital Controller Product Manual  3/07 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
OUTLoLIM 
 
LOW OUTPUT LIMIT—This is the lowest value of 
output below which you do not want the controller 
automatic output to exceed. 
 
  0 % to 100 %  
–5 % to 105 % 
For relay output types.  
For current output types 
I Hi LIM 
Within the range of the 
output limits 
HIGH RESET LIMIT—This is the highest value of 
output beyond which you want no reset to occur. 
I Lo LIM 
Within the range of the 
output limits 
LOW RESET LIMIT—This is the lowest value of 
output beyond which you want no reset to occur. 
DROPOFF 
–5 to 105 % of output 
CONTROLLER DROPOFF VALUE—Output value 
below which the controller output will drop off to the 
low output limit value set in prompt OUTLoLIM. 
DEADBAND 
 
DEADBAND—An adjustable gap between the 
operating ranges of output 1 and output 2 in which 
neither output operates (positive value) or both 
outputs operate (negative value). 
 
–5.0 to 25.0 %  Time Duplex 
FAILMODE 
 
 
NoLATCH 
 
LATCH 
FAILSAFE MODE—How the controller operates 
during a Failsafe condition. 
NON-LATCHING—Controller stays in last mode 
(automatic or manual); output goes to failsafe value. 
LATCHING—Controller goes to manual mode; 
output goes to failsafe value. 
FAILSAFE 
0 to 100 % 
FAILSAFE OUTPUT 2 VALUE—The value used 
here will also be the output level when you have 
Communications SHED set to failsafe or when NO 
BURNOUT is configured and the PV Source fails. 
 ATTENTION   At power-up, the Loop 2 Output is set 
to the Failsafe Output 2 value. 
NOTE 1: If PV source is one of the Analog Inputs, then the SP HiLIM and SP LoLIM values must be 
between the Input High and Input Low values for the input type configured.  If the PV source is an Input 
Algorithm configured for: 
•  Carbon Potential, then the SP HiLIM and SP LoLIM values must be between 0.000 and 2.000 
•  Dewpoint, then the SP HiLIM and SP LoLIM values must be between –50 and +100 
•  Oxygen, then the SP HiLIM and SP LoLIM values must be between 0 to 40.00 
•  Weighted Average, Summer, Subtractor, High or Low, then the SP HiLIM and SP LoLIM values 
must be between the configured CALC HI and CALC LOW values. CALC HI and CALC LOW can 
be set anywhere between –999 and 9999. 
•  Math A, Math B, Math C or Math D, then the SP HiLIM and SP LoLIM values can be set 
anywhere between –999 and 9999 and are not limited to the CALC HI and CALC LOW values.