Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  153 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
C2 RANGE 
4-20mA  
0-20mA 
SECOND CURRENT OUTPUT RANGE—Allows the 
user to easily select 4-20mA output or 0-20mA 
output operation without the need for recalibration of 
the instrument. 
 ATTENTION   Changing the Current Output Range 
will result in the loss of Field Calibration values and 
will restore Factory Calibration values. 
LOW VAL 
Low Scale Value within 
the range of the selected 
variable to represent the 
minimum output (0 or 4 
mA) 
OUTPUT LOW SCALING FACTOR—This is a value 
in engineering units used to represent all configured 
parameters except Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %. However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
HIGH VAL 
High Scale Value within 
the range of the selected 
variable to represent the 
maximum output (20 mA) 
OUTPUT HIGH SCALING FACTOR—This is a 
value in engineering units used to represent all 
configured parameters except Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %. However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
CUR OUT3 
 ATTENTION  
Prompts for the Third 
Current Output 
Selection appear only 
when the Third 
Current Output option 
is installed. 
Same selections as for 
CUR OUT2 
THIRD CURRENT OUTPUT SELECTION—
Provides a milliamp output representing one of 
several control parameters. The display for Third 
Current Output viewing will be in engineering units 
for all but output. Output will be displayed in percent. 
ATTENTION Other prompts affected by these 
selections: 4mA VAL and 20mA VAL. 
ATTENTION When Loop 2 Output is configured for 
CURRENT, the Third Current Output is forced to 
“OUTPUT 2”. 
ATTENTION CB OUT should not be used for Three 
Position Step Control or Position Proportional 
Control applications. 
C3 RANGE 
4-20mA  
0-20mA 
THIRD CURRENT OUTPUT RANGE—Allows the 
user to easily select 4-20mA output or 0-20mA 
output operation without the need for recalibration of 
the instrument. 
 ATTENTION   Changing the Current Output Range 
will result in the loss of Field Calibration values and 
will restore Factory Calibration values.