Configuration
3/07 UDC3500 Universal Digital Controller Product Manual 155
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
TO HOLD
TO HOLD—Contact closure suspends Setpoint
Program or Setpoint Ramp. When contact reopens,
the controller starts from the Hold point of the
Ramp/Program unless the Ramp/Program was not
previously started via the
Run/Hold key.
This selection applies to either loop.
ATTENTION When multiple SP Programs are
enabled, this configuration is affected by the “SPP
A” and “SPP B” configurations below.
TO PID2
TO PID2—Contact closure selects PID Set 2.
TO PID3
TO PID3—Contact closure selects PID Set 3.
TO PID4
TO PID4—Contact closure selects PID Set 4.
PV 2IN
PV=INPUT 2—Contact closure selects PV = Input 2.
PV 3IN
PV=INPUT 3—Contact closure selects PV = Input 3.
RERUN
RERUN—Allows the Setpoint Programmer to be
reset to the initial segment of its current cycle, unit
stays in previous mode.
ATTENTION When multiple SP Programs are
enabled, this configuration is affected by the “SPP
A” and “SPP B” configurations below.
TO RUN
RUN—Contact closure starts a stopped SP Ramp or
Program. Upper left character blinks “R”. Reopening
the contact has no effect.
This selection applies to either loop.
ATTENTION When multiple SP Programs are
enabled, this configuration is affected by the “SPP
A” and “SPP B” configurations below.