Configuration 
160  UDC3500 Universal Digital Controller Product Manual  3/07 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
 
+TO SP1 
PLUS SETPOINT 1—Contact closure puts the 
controller to Local Setpoint 1. 
 
+RUN 
PLUS RUN SETPOINT PROGRAM/RAMP—
Contact closure starts SP Program/Ramp if enabled. 
 
+To SP3 
PLUS SETPOINT 3 —Contact closure puts the 
controller to local setpoint 3. 
DIG INP2 
Same selections as for 
Digital Input 1 
DIGITAL INPUT 2 SELECTIONS 
DIG2COMB 
Same selections as Digital 
Input 1 Combinations 
DIGITAL INPUT 2 COMBINATIONS 
DIG INP3 
Same selections as for 
Digital Input 1 
DIGITAL INPUT 3 SELECTIONS 
DIG INP4 
Same selections as for 
Digital Input 1 
DIGITAL INPUT 4 SELECTIONS 
Dion LP2 
 
DIGITAL INPUTS ON LOOP 2—Used when Two 
Loops or Internal Cascade are configured. Digital 
Inputs are assigned to Loop 2 per this configuration. 
All other Digital Inputs are assigned to Loop 1 
 
NONE 
DI 2  
DI 2, 3  
DI2, 3, 4 
NONE—No Digital Inputs on Loop 2, all on Loop 1 
DI 2—Assign Digital Input 2 to Loop 2 
DI 2,3—Assign Digital Inputs 2 and 3 to Loop 2  
DI 2,3,4—Assign Digital Inputs 2, 3 and 4 to Loop 2 
 ATTENTION  When Setpoint Program is configured 
to operate on both control loops, then any digital 
input configured for TO RUN, TO HOLD, RERUN, or 
To BEGIN will control the setpoint program 
regardless of the loop to which the Digital Input is 
assigned.