Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  163 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
 
TO MAN 
TO MAN—MANUAL MODE, SAME OUTPUT 
The controller will return to manual mode at the 
same output level that it had before shed. 
 
FSAFE 
FSAFE—MANUAL MODE, FAILSAFE OUTPUT 
The controller will return to manual mode at the 
output value selected at Control prompt FAILSAFE. 
 
TO AUTO 
TO AUTO—AUTOMATIC MODE, LAST SP 
The controller will return to the automatic mode and 
the last setpoint used before shed. 
SHED SP 
 
SHED SETPOINT RECALL—The instrument will 
control to the selected Setpoint following a Shed. 
(controller switches from using CSP to LSP) 
 ATTENTION  If SHEDENAB is configured for 
DISABLE, then this prompt will not be configurable. 
NOTE: if a RSP is the current setpoint, a CSP 
override will not be used. CSP overrides local 
setpoint only. 
 
TO LSP 
TO LSP—When a Shed occurs, the controller 
switches from slave to monitor mode and uses the 
last local setpoint prior to the slave mode. The CSP 
value is disregarded on Shed. 
 
TO CSP 
TO CSP—When a SHED timeout occurs, the 
controller switches from slave to monitor mode and 
uses the local setpoint that is set equal to the CSP 
value. 
UNITS 
 
ENG 
PERCENT 
COMPUTER SETPOINT UNITS 
ENG—Engineering units 
PERCENT—Percent of PV range 
CSP RATO 
–20.0 to 20.0 
COMPUTER SETPOINT RATIO—Computer 
setpoint ratio for Loop 1. 
CSP BIAS 
–999. to 9999.  
(engineering units) 
COMPUTER SETPOINT BIAS—Computer setpoint 
bias in Engineering Units for Loop 1. 
CSP2RATO 
–20.0 to 20.0 
LOOP 2 COMPUTER SETPOINT RATIO—
Computer setpoint ratio for Loop 2. 
CSP2BIAS 
–999. to 9999.  
(engineering units) 
LOOP 2 COMPUTER SETPOINT BIAS—Computer 
setpoint bias in Engineering Units for Loop 2.