Monitoring and Operating the Controller 
206  UDC3500 Universal Digital Controller Product Manual  3/07 
Position Proportional applications, as it reduces “hunt” problems for the motor. This 
selection is also recommended for applications that have significant deadtimes. 
For the FAST selection, the controller calculates aggressive tuning constants with the 
objective of producing quarter-damped response. Depending upon the process, this 
selection will usually result in some overshoot. For this reason, it may be desirable to 
enable the FUZZY tune selection. See Section 4.11. When Fuzzy tune is enabled, it will 
work to suppress or eliminate any overshoot that may occur as a result of the calculated 
tuning parameters as the PV approaches the setpoint. This selection is best suited for 
processes with a single lag or for those that do not have any appreciable deadtime. 
FUZZY tuning does not work well for processes that have appreciable deadtime. 
The Accutune III tuning process will cycle the controller’s output two full cycles 
between the low and high output limits while allowing only a very small Process 
Variable change above and below the SP during each cycle. A “T” shows in the upper 
display until tuning is completed. 
At the end of the tuning process, the controller immediately calculates the tuning 
constants and enters them into the Tuning group, and begins PID control with the correct 
tuning parameters. This works with any process, including integrating type processes, 
and allows retuning at a fixed setpoint.