Monitoring and Operating the Controller
228 UDC3500 Universal Digital Controller Product Manual 3/07
Step Operation Press Result
3
Select PD +
Manual Reset
Function
or
To select
PD+MR— PD + Manual Reset
4
Select Control
Set-up Group
Setup
Until you see:
Upper Display = SET
Lower Display = CONTROL
5
Select PID SETS
Func
Loop 1/2
Until you see:
Upper Display = (available selections)
Lower Display = PID SETS
6
Select PID SETS
Function
or
To select
2KEYBD—2 sets, keyboard selectable
7
Select LSP’S
Func
Loop 1/2
Until you see:
Upper Display = (available selections)
Lower Display = LSP’S
8
Select LSP’S
Function
or
To select
TWO—Two LSP’s
9
Select SP TRACK
Func
Loop 1/2
Until you see:
Upper Display = (available selections)
Lower Display = SP TRACK
10
Select SP TRACK
Function
or
To select
NONE—No SP Tracking
11
Select Tuning
Set-up Group
Setup
Until you see:
Upper Display = SET
Lower Display = TUNING
12
Select Manual
Reset Value
Func
Loop 1/2
Until you see:
Upper Display = (available selections)
Lower Display = MAN RSET
13
Configure Manual
Reset Value
or
To configure:
0— Manual Reset Value
A Manual Reset of 0 is for no output bias and requires that
LSP2 = 0 % of the Setpoint Range. If bias is required, set
the Manual Reset value to equal the desired output bias
value.
14
Select Algorithm
Set-up Group
Setup
Until you see:
Upper Display = SET
Lower Display = ALGORTHM
15
Select Control
Algorithm
Func
Loop 1/2
Until you see:
Upper Display = (available selections)
Lower Display = CONT ALG
16
Select PID A
or
To select:
PID A— PID A
This is defining the back-up control algorithm.