EasyManua.ls Logo

Honeywell UDC3500 - Page 32

Honeywell UDC3500
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
16 UDC3500 Universal Digital Controller Product Manual 3/07
Environmental and Operating Conditions
Parameter Reference Rated Operative
Limits
Transportation and Storage
Ambient Temperature
25 ± 3 °C
77 ± 5 °F
15 to 55 °C
58 to 131 °F
0 to 55 °C
32 to 131 °F
–40 to 66 °C
–40 to 151 °F
Relative Humidity
10 to 55* 10 to 90* 5 to 90* 5 to 95*
Vibration
Frequency (Hz)
Acceleration (g)
0
0
0 to 70
0.4
0 to 200
0.6
0 to 200
0.5
Mechanical Shock
Acceleration (g)
Duration (ms))
0
0
1
30
5
30
20
30
Line Voltage (Vdc)
24 Vdc
+24 ± 1
22 to 27
20 to 30
- -
Line Voltage (Vac)
90 to 240 Vac
24 Vac
120 ± 1
240 ± 2
24 ± 1
90 to 240
20 to 27
90 to 264
20 to 27
- -
- -
- -
Frequency (Hz)
(For Vac)
50 ± 0.2
60 ± 0.2
49 to 51
59 to 61
48 to 52
58 to 62
- -
- -
* The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is derated to
maintain constant moisture content.