Troubleshooting/Service 
3/07  UDC3500 Universal Digital Controller Product Manual  319 
Step  What to do  How to do it 
3c 
Third Current Output: Test for 
operation. 
Change Options Set Up group function prompt 
CUR3 OUT = OUTPUT  
Make the Current #3 Options Set up group 
function prompt CO RANGE = 4–20 
Go to Step 4 
4 
Check the output.  Put the controller into Manual mode and 
change the output via the front keyboard from 
0 % to 100 %. Use a DC milliammeter at the 
rear terminals for the output being diagnosed 
to verify the output. 
Output works correctly: Return the controller 
to its original configuration and check output 
again. 
Output does not work correctly: Go to Step 5. 
5 
Restore Factory Calibration  For the output being diagnosed, change the 
CO RANGE prompt from its present setting to 
its other setting. Exit the setup group and then 
return and change CO RANGE back to its 
previous setting. 
Output works correctly: Finished 
Output does not work correctly: Go to Step 6. 
6 
Field Calibrate the output.  Refer to Section 
1 – Output Calibration for 
details.  
Output works correctly: Finished 
Output does not work correctly: Go to Step 7. 
7 
Change Current Output board. 
Installation instructions provided with new 
board.