Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  79 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
 
PID A 
 ATTENTION   PID A 
should not be used for 
Proportional only action; 
i.e., no integral (reset) 
action. Instead, use 
PD+MR with rate set to 0. 
PID A—This normally used for three-mode control. 
Three mode control means that the output can be 
adjusted to be at any point between 0 % and 100 %. 
It applies all three control actions—Proportional (P), 
Integral (I), and Derivative (D)—to the error signal. 
Proportional (Gain)
—Regulates the controller’s 
output in proportion to the error signal (the difference 
between Process Variable and Setpoint). 
Integral (Reset
)—Regulates the controller’s output 
to the size of the error and the time the error has 
existed. (The amount of corrective action depends 
on the value of proportional Gain.) 
Derivative (Rate)
—Regulates the controller’s output 
in proportion to the rate of change of the error. (The 
amount of corrective action depends on the value of 
proportional Gain.) 
 
PID B 
PID B—Unlike the PID A equation, the controller 
gives only an integral response to a setpoint change, 
with no effect on the output due to the gain or rate 
action, and it gives full response to PV changes. 
Otherwise controller action is as described for the 
PID A equation. See note on PID A. 
 PD+MR 
PD WITH MANUAL RESET—This is used whenever 
integral action is not wanted for automatic control 
action. The equation is computed with no integral 
contribution. The MANUAL RESET value, which is 
operator adjustable, is then added to the present 
output to form the controller output. 
Switching between manual and automatic mode is 
bumpless (output does not change value). 
If you select PD with Manual Reset you can also 
configure the following variations: 
  •  PD (Two Mode) control, 
  •  P (Single Mode) control. 
Set Rate (D) to 0. 
 ATTENTION Other prompts affected: MAN RSET 
in the Tuning Set Up group