7 Configuration
Voltage 0 to 1 V Voltage signal
Voltage -1 to +1 V Voltage signal
Voltage 0 to 10 V Voltage signal
Voltage -10 to +10 V Voltage signal
Current 0to20mA Current signal
Default setting for analog input 1 to 3
Current 4 to 20 mA Current signal
Temperature in-
put
In the case of a voltage/current signal, resistance/potentiometer, or resistance
transmitter, the measured value must be defined as a temperature to convert auto-
matically when changing the temperature unit.
No Measured value is not a temperature.
Yes Measured value is a temperature.
Unit Measured value unit for voltage/current signal, resistance/potentiometer or resis-
tance transmitter
%
(Max. 5 characters)
The unit is displayed if the measured val-
ue is displayed in numerical form
Linearization Available options and default settings depend on the measuring sensor selected.
Linear
Pt50 IEC 751: 2008
Pt100 IEC 751: 2008
Pt500 IEC 751: 2008
Pt1000 IEC 751: 2008
Pt100 JIS JIS 1604
Pt50 GOST GOST 6651-2009 A.2
Pt100 GOST GOST 6651-2009 A.2
Cu50 GOST GOST 6651-2009 A.3
Cu100 GOST GOST 6651-2009 A.3
Ni100 DIN 43760:1987-09
Ni100 GOST GOST 6651-2009 A.5
Fe-CuNi L DIN 43710:1985-12
Fe-CuNi J DIN EN 60584-1:2014
Cu_CuNi U DIN 43710:1985-12
Cu-CuNi T DIN EN 60584-1:2014
NiCr-Ni K DIN EN 60584-1:2014
NiCr-CuNi E DIN EN 60584-1:2014
NiCrSI-NiSi N DIN EN 60584-1:2014
Pt10Rh-Pt S DIN EN 60584-1:2014
Pt13Rh-Pt R DIN EN 60584-1:2014
Pt30Rh-Pt6Rh B DIN EN 60584-1:2014
W5Re-W26Re C ASTM E230M-11
W3Re-W25Re D ASTM E1751M-09
W5Re-W20Re A1 GOST R 8.585-2001
Chromel®-Copel® L GOST R 8.585-2001
Chromel®-Alumel® GOST R 8.585-2001
Platinel II
Parameter Selection/settings Description