EasyManua.ls Logo

LOYTEC L-INX - 10.3 M-Bus Network

Default Icon
305 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-INX User Manual 212 LOYTEC
Version 4.0 LOYTEC electronics GmbH
Figure 164: Connecting L-MBUS over console connector.
10.2.2 Extension Port
Devices that do not have a serial console connector provide an extension port marked EXT
on the device as shown in Figure 165. Those devices need to use the L-MBUS converter.
On the L-MBUS set the jumper as indicated on the front label. Follow the cabling
instructions of Figure 165 between the EXT port of the L-INX and the PORT1 on the
L-MBUS.
Figure 165: Connecting L-MBUS over the extension port.
10.3 M-Bus Network
The M-Bus network utilizes a two-wire connection. Several M-Bus slave devices are
connected in parallel to the transmission medium. Each M-bus device has a primary address
in the range from 0 to 250. This primary address must be unique for each device. Also a
secondary address can be used for the slave devices. The secondary addressing mode is

Table of Contents