EasyManua.ls Logo

LOYTEC L-INX - DIP Switch Settings; Terminal Layout and Power Supply; Linx-10 X;11 X; Linx-20 X;21 X

Default Icon
305 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-INX User Manual 48 LOYTEC
Version 4.0 LOYTEC electronics GmbH
3.7 DIP Switch Settings
The DIP switch assignment for the device is shown in Table 5. Please leave all switches at
default state. Note, that the L-INX models 12X, 15X, 22X do not have DIP switches.
DIP Switch #
Function
Factory Default
1
Must be OFF
OFF
2
Must be OFF
OFF
3
Must be ON
ON
4
Must be OFF
OFF
5
Must be OFF
OFF
6
Must be OFF
OFF
7
M-Bus enable
OFF
Table 5: DIP Switch Settings.
3.8 Terminal Layout and Power Supply
3.8.1 LINX-10X/11X
The LINX-10X/11X provides pluggable screw terminals to connect to the network as well
as to the power supply. The screw terminals can be used for wires of a maximum thickness
of 2.5 mm
2
/AWG12. The device can either be DC or AC powered.
Terminal
Function
1
Modbus RS-485 Ground
2
Modbus RS-485 Non-Inverting Input
3
Modbus RS-485 Inverting Input
4
Earth Ground
5, 6
CEA-709 A, B of TP/FT-10 Channel Port
8
Ethernet 100Base-T
15
Earth Ground
16, 17
Power Supply 12 35 VDC or 12 24 VAC ± 10 %
Do not connect terminal 17 to earth ground!
Table 6: LINX-10X/11X Terminals.
3.8.2 LINX-20X/21X
The LINX-20X/21X provides pluggable screw terminals to connect to the network as well
as to the power supply. The screw terminals can be used for wires of a maximum thickness
of 2.5 mm
2
/AWG12. The device can either be DC or AC powered.

Table of Contents