L-INX User Manual 22 LOYTEC
Version 4.0 LOYTEC electronics GmbH
L-INX
Model
Features
100
101
110
111
120
121
150
151
200
201
210
211
220
221
CEA-709 Router
CEA-709 RNI
CEA-709 (FT)
1
1
1
1
CEA-852 (IP)
1
1
1
1
BACnet Router
BACnet MS/TP
2
2
2
2
BACnet IP
2
2
2
2
Modbus RTU
3
3
3
3
3
3
Modbus IP
M-Bus
OPC XML-DA Server
PLC (IEC 61131)
LIOB Connect
LIOB FT
LCD Display
Serial Console
SD Card, USB
Ethernet Switch/Hub
1
This model can be configured to have either FT or IP active for CEA-709.
2
This model can be configured to have either MS/TP or IP active for BACnet.
3
Modbus RTU can only be used, if BACnet MS/TP is not active on this model.
Table 1: Available features in different L-INX models
On models without the router option, certain ports can only be used alternatively. On CEA-
709 models this means either as CEA-709 FT or as CEA-852 IP (see note 1 in Table 1). On
BACnet models this means either as BACnet MS/TP or as BACnet IP (see note 2 in Table
1). Some BACnet models have a restriction on Modbus RTU and BACnet MS/TP as they
share the same port. On those models Modbus RTU can only be used, if BACnet MS/TP is
disabled (see note 3 in Table 1).
1.8 Scope
This document covers L-INX devices with firmware version 4.0 and the L-INX
Configurator version 4.0 and higher. The usage of logiCAD itself is beyond the scope of
this manual. Please refer to the logiCAD online help in case of additional questions.