L-INX User Manual 303 LOYTEC
Version 4.0 LOYTEC electronics GmbH
Environmental Protection IP 40 (enclosure); IP 20 (screw terminals)
Installation DIN rail mounting (EN 50 022) or wall
mounting
18.2 Resource Limits
Table 18 specifies the resource limits of the different L-INX models.
L-INX
Model
Limits
10X
11X
12X
15X
20X
21X
22X
Total number of data points
10,000
10,000
30,000
30,000
10,000
10,000
30,000
OPC Tags
2,000
n/a
5,000
5,000
2,000
n/a
5,000
User Registers
1,000
1,000
1,000
1,000
1,000
1,000
1,000
NVs (static, dynamic)
1,000
1,000
1,000
1,000
n/a
n/a
n/a
External NVs
1,000
1,000
1,000
1,000
n/a
n/a
n/a
Alias NVs (ECS and legacy
mode)
1,000
1,000
1,000
1,000
n/a
n/a
n/a
Address table entries/legacy
512/
15
1,000/
15
1,000/
15
1,000/
15
n/a
n/a
n/a
LONMARK Calendar objects
1 (25 calendar patterns)
n/a
n/a
n/a
LONMARK Scheduler
objects
100 (max. AST configuration size 384KB,
64 data points per scheduler)
n/a
n/a
n/a
LONMARK Alarm Servers
1
1
1
1
n/a
n/a
n/a
BACnet objects (analog,
binary, multi-state)
n/a
n/a
n/a
1,000
750
750
1,000
BACnet client mappings
n/a
n/a
n/a
1,000
750
750
1,000
BACnet scheduler objects
n/a
n/a
n/a
100
100
100
100
BACnet calendar objects
n/a
n/a
n/a
25
25
25
25
BACnet notification classes
n/a
n/a
n/a
32
32
32
32
Trend Logs
100
100
100
100
100
100
100
Total trended data points
256
256
256
256
100
100
100
Total aggregated size
6MB
6MB
60MB
60MB
6MB
6MB
60MB
E-mail templates
100
100
100
100
100
100
100
Math objects
100
100
100
100
100
100
100
Alarm Logs
10
10
10
10
10
10
10
Modbus data points
2,000
2,000
2,000
2,000
2,000
2,000
2,000
M-Bus data points
1,000
1,000
1,000
1,000
1,000
1,000
1,000
Connections
1,000
1,000
2,000
2,000
1,000
1,000
2,000
Table 18: Resource limits of different L-INX models