EasyManua.ls Logo

Moog ACV Series - Analog Inputs; Figure 34: Analog Inputs

Moog ACV Series
364 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Moog ACV with CANopen bus interface 6 Signal routing and scaling
Analog inputs
B99224-DV018-D-211, Rev. A, October 2018 86
6.4 Analog inputs
The following figure shows the available inputs and the physical connector names. All analog to digital con-
verters have the same resolution of 12 bit.
Figure 34: Analog inputs
Document CA63420-001 "User Manual Electrical Interfaces".
The analog input 0 is intended for the spool position setpoint value and the analog input 1 is intended for the
pressure setpoint value. The analog inputs 0 and 1 will only be routed to the demand value generators, if the
<DeviceMode> (0x6042) is set to 2 (setpoint input locally). The setpoint values are provided by the field bus, if
the <DeviceMode> (0x6042) is set to 1 (setpoint input via bus). In this case the analog inputs 0 and 1 can be
used as additional inputs for external transducers.
Chapter "6.2.3 Spool position setpoint value path", page 59
An external transducer on analog input 0, 1, 2, 3 or 4 can be scaled and mapped as input for the controller by
using the transducer interface.
Chapter "6.3.9 Transducer interface definition", page 74
p
u
Analog input 2
Analog input 3
Analog input 4
Analog input 1
Analog input 0
Internal pressure
transducer in
port A
Connector
X1
Connector
X1
Connector
X5
Connector
X7
p
u
p
u
p
u
p
u
Connector
X6
pA
u
<Value>
(0x3404)
<AnaInpActualValue0>
(0x3204)
<AnaInpActualValue1>
(0x320C)
<AnaInpActualValue2>
(0x3214)
<AnaInpActualValue4>
(0x3224)
<AnaInpActualValue3>
(0x321C)
Internal
Chapter 6.4.6
Chapter 6.4.1
Chapter 6.4.2
Chapter 6.4.3
Chapter 6.4.4
Chapter 6.4.5
The analog inputs 0 and 1 are only effective as setpoint value inputs, if the <DeviceMode>
(0x6042) is set to 2 (setpoint input locally).

Table of Contents