Moog ACV with CANopen bus interface 8 Diagnostics
Troubleshooting
B99224-DV018-D-211, Rev. A, October 2018 287
8.4.1.30 0x3A: Factory data memory corrupted
8.4.1.31 0x3C: Diagnosis data memory corrupted
8.4.1.32 0x3D: Position control monitoring
Error Code: 0x3A
Error Name: Factory data memory corrupted
Description: Internal error during initialization of factory parameter settings occurred
Severity of error: Major
Action: Restart the valve
If the error still occurs after restarting the valve, send the valve back to factory for
service.
Error Code: 0x3C
Error Name: Diagnosis data memory corrupted
Description: Internal error during initialization of diagnose parameter settings occurred
Severity of error: Minor
Action: Restart the valve
If the error still occurs after restarting the valve, send the valve back to factory for
service.
Error Code: 0x3D
Error Name: Position control monitoring
Description: An axis position control monitoring fault is detected. The current axis position control
deviation exceeds the adjusted limits.
Severity of error: Application specific
Action: Check adjusted deviation limits
Check position
Check sensor adjustments and settings
Check interface configuration
This fault reaction is available for Axis Control Valves (ACV) only.
In order to make a customer configured fault reaction working, the axis position monitoring must
be switched on.
Chapter "7.15.3 Axis position control deviation monitoring", page 237