Parameter Specification Tables C-13
DC590+ Series DC Digital Drive
Tag Mn MMI Block Name MMI Parameter Name Minimum Maximum Default Units Range Notes
368 k8 LINK 3 SOURCE TAG -1276 1276 0 V0 W2
369 k9 LINK 3 DESTINATION TAG 0 1276 0 V0 W2
370 ka LINK 4 SOURCE TAG -1276 1276 0 V0 W2
371 kb LINK 4 DESTINATION TAG 0 1276 0 V0 W2
374 ke SEQUENCING SYSTEM RESET 0 1 0 V0 W4
375 kf SETPOINT SUM 1 LIMIT 0.00 200.00 105.00 % V0 W0
376 kg SEQUENCING DRIVE RUNNING 0 1 0 V0 W4
379 kj miniLINK VALUE 8 -300.00 300.00 0.00 % V1 W0
380 kk miniLINK VALUE 9 -300.00 300.00 0.00 % V1 W0
381 kl miniLINK VALUE 10 -300.00 300.00 0.00 % V1 W0
382 km miniLINK VALUE 11 -300.00 300.00 0.00 % V1 W0
383 kn miniLINK VALUE 12 -300.00 300.00 0.00 % V1 W0
384 ko miniLINK VALUE 13 -300.00 300.00 0.00 % V1 W0
385 kp miniLINK VALUE 14 -300.00 300.00 0.00 % V1 W0
390 ku LINK 11 SOURCE TAG -1276 1276 0 V0 W2
391 kv LINK 43 DESTINATION TAG 0 1276 0 V0 W2
392 kw ADVANCED 1 ADVANCED 0 1 0
0: OFF
1: ON
V0 W0
393 kx ADVANCED 1 MODE 0 6 0
0: SWITCH
1: INVERT
2: AND
3: OR
4: SIGN CHANGER
5: MODULUS
6: COMPARATOR
V0 W0
394 ky LINK 41 AUX.SOURCE -1276 1276 0 V0 W2
395 kz LINK 12 SOURCE TAG -1276 1276 0 V0 W2
396 l0 LINK 44 DESTINATION TAG 0 1276 0 V0 W2
397 l1 ADVANCED 2 ADVANCED 0 1 0
0: OFF
1: ON
V0 W0
398 l2 ADVANCED 2 MODE 0 6 0 See Tag 393 V0 W0
399 l3 LINK 42 AUX.SOURCE -1276 1276 0 V0 W2
400 l4 LINK 30 PID O/P DEST 0 1276 0 V0 W2
401 l5 PID DERIVATIVE TC 0.000 10.000 0.000 s V1 W0
402 l6 PID INT.TIME.CONST 0.01 100.00 5.00 s V1 W0