Ethernet 8-31
AC30 series Variable Speed Inverters
Peer to Peer Parameter Summary
Note: The value of the Peer to Peer configuration parameters only become active when the Peer to Peer module initialises, i.e. on inverter power-
up or transition of the parameter 1725 Peer to Peer Enable to TRUE.
Parameter Name No. Path Default Range Units Writable
Peer to Peer Enable
172
5
Setup::Communications::Peer
to Peer Parameters::Base
Comms::Peer to Peer
FALSE FALSE
TRUE
ALWAYS
Peer to Peer Parameter.
Enables the Peer to Peer module.
Destination IP Address
172
6
Setup::Communications::Peer
to Peer Parameters::Base
Comms::Peer to Peer
255.255.255.
255
0.0.0.0 to
255.255.255.255
ALWAYS
Peer to Peer Parameter.
Sets the destination IP address of the data when the Peer to Peer module is sending. If the Destination
IP Address is set to 255.255.255.255 then the sent data is broadcast and all listening inverters will
receive the data.
Destination Port
172
7
Setup::Communications::Peer
to Peer Parameters::Base
Comms::Peer to Peer
1250
1 to
65535
ALWAYS
Peer to Peer Parameter.
Sets the UDP port number the Peer to Peer module sends data to. Normally this will be set the same as
the Local Port.
Local Port
172
8
Setup::Communications::Peer
to Peer Parameters::Base
Comms::Peer to Peer
1250 1 to
65535
ALWAYS
Peer to Peer Parameter.