Fieldbuses A-17
AC30 series Variable Speed Inverter
4. Enter the Name and IP address of the inverter. Set the Comm Format as Data SINT. The Input Assembly Instance is 100 and in this
example the data size is a total of 6 bytes. The Output Assembly Instance is 150 and in this example the data size is a total of 6 bytes.
The mapping sizes on the inverter MUST match that on the PLC. Set the Configuration Assembly Instance to 128 size 0.
5. Within the Controller Tags the communications data arrays are automatically created: