A-36 Fieldbuses
AC30 series Variable Speed Inverter
If the input and output mappings have invalid entries then the parameter 3143 PROFINET State will report ERROR and the inverter will not go
into the Operational state. The parameter 3144 PROFINET Diagnostic can be used to determine which mapping table has an invalid entry.
Note: On the PLC all output modules must be plugged before input modules.
GSD File
The latest PROFINET GSD file for the inverter may be downloaded from www.parker.com
The GSD file may also be downloaded directly from the drive via a web browser. To access this make sure the parameter 0944 Web Access is
set to LIMITED or FULL.
Enter the inverter IP address into the web browser and access the web page “Services” and under PROFINET GSDML file click the Download
button. Altenatively type the following into the browser address bar (replacing ip_address with the inverter’s IP address):
ip_address/eds/pnio.zip
The GSD file has the default mapping modules are ready plugged. This may be modified within the PLC configuration tool as required.