Fieldbuses A-47
AC30 series Variable Speed Inverter
7. Set the Station Name of the inverter if it is not already set:
Make sure the inverter is connected to the network and PROFINET is enabled. Go online with the PLC and right-click on the PN-Controller
and select Scan for Devices… The Station Name of the required device can be modified. Select Set Name+IP for this to take effect.
Note that the device may also be added from this dialog box rather than adding it manually.
8. Build the project and go online.