C-162 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Sramp Jerk 1
0493
Parameters::Motor Control::Ramp
10.0
0.0 to 100.0
%/s³
ALWAYS
Rate of change of acceleration for the first segment of the curve in units of percent per second³, i.e. if the full speed of the machine is
1.25m/s then the jerk will be:
1.25 x 50.00% = 0.625m/s³
Sramp Jerk 2
0494
Parameters::Motor Control::Ramp
10.0
0.0 to 100.0
%/s³
ALWAYS
Rate of change of acceleration in units of percent per second³ for segment 2
Sramp Jerk 3
0495
Parameters::Motor Control::Ramp
10.0
0.0 to 100.0
%/s³
ALWAYS
Rate of change of acceleration in units of percent per second³ for segment 3
Sramp Jerk 4
0496
Parameters::Motor Control::Ramp
10.0
0.0 to 100.0
%/s³
ALWAYS
Rate of change of acceleration in units of percent per second³ for segment 4
Ramp Hold
0497
Parameters::Motor Control::Ramp
FALSE
ALWAYS
When TRUE the output of the ramp is held at its last value
Ramping Active
0498
Parameters::Motor Control::Ramp
NEVER
Set TRUE when ramping.
Ramp Spd Setpoint Input
0499
Parameters::Motor Control::Ramp
x.x
-200.0 to 200.0
%
NEVER
Input speed setpoint to the ramp