Parameter Reference C-185
AC30 series Variable Speed Drive
Output A Invert
1291
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS
Inverts the value from Output A when "1679 Output Source" is set to DIGITAL OUTPUTS
Output B Invert
1292
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS
Inverts the value from Output B when "1679 Output Source" is set to DIGITAL OUTPUTS
Output Z Invert
1293
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS
Inverts the value from Output Z when "1679 Output Source" is set to DIGITAL OUTPUTS
Output Z Invert
1870
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS
TRUE to FALSE to validate the actual position of the Synthetic encoder as the Zero position. Synthetic encoder output will generate a
Zpulse every turn. Synthetic encoder position is reset to Zero. The position is validated on a TRUE to FALSE change of this parameter.
If MAIN SPD FEEDBACK, the Z pulse position is kept in memory during power cycle.
Output Z Invert
1871
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS
Synthetic encoder count. Values are limited to +/- 1024 turns.
Only available if the Output Source of the retransmit Output is set to MAIN SPD FEEDBACK.
Valus is reset to Zero on a TRUE to FALSE transition of the Z pulse Input.
Output Z Invert
1872
Parameters::System Board::SB
Retransmit
FALSE
ALWAYS