Parameter Reference C-225
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Enable 33 - 64
0730
Parameters::Trips::Trips Status
FFFFFFFF
0:33 A1
1:34 A2
2:35 A3
3:36 A4
4:37 A5
5:38 A6
6:39 A7
7:40 A8
8:41 SPEED ERROR
9:42 PEERTOPEER OVERRUN
10:43 PHASE CONFIG
11:44 FIELDBUS BREAK
14:47 CURRENT IMBALANCE
16:49 APPLICATION
18:51 CPU USAGE
ALWAYS
A 32-bit word that can be used to enable, (or disable), individual trips. Bit 0 of this word corresponds to trip 33, up to bit 31 of this word
which corresponds to trip 64.
Refer to Chapter 10 “Trips and Fault Finding” for details of the value corresponding to each trip.