Parameter Reference C-259
AC30 series Variable Speed Drive
1636
Manufacturing Flags
Parameters::Device Manager::Drive info
WORD
NEVER
ENGINEER
03799
1637
Engineer Password
Parameters::Keypad::Graphical Keypad
WORD
0000
ALWAYS
TECHNICIAN
03801
1640
Modbus Password
Setup::Communications::Option
Parameters::Option Comms::Modbus RTU
WORD
0000
ALWAYS
TECHNICIAN
4
03807
1641
VDC Lim Enable
Parameters::Motor Control::DC Link Volts Limit
BOOL
FALSE
STOPPED
TECHNICIAN
03809
1642
VDC Lim Level
Parameters::Motor Control::DC Link Volts Limit
REAL
91.0
78.0 to 100.0
%
STOPPED
TECHNICIAN
03811
1643
VDC Lim Active
Parameters::Motor Control::DC Link Volts Limit
BOOL
NEVER
TECHNICIAN
03813
1644
VDC Lim Output
Parameters::Motor Control::DC Link Volts Limit
REAL
x.x
Min to Max
Hz
NEVER
ENGINEER
03815
1645
Pwrl Enable
Parameters::Motor Control::Power Loss Ride Thru
BOOL
FALSE
STOPPED
TECHNICIAN
03817
1646
Pwrl Trip Threshold
Parameters::Motor Control::Power Loss Ride Thru
REAL
52.0
20.0 to 60.0
%
STOPPED
TECHNICIAN
03819
1647
Pwrl Control Band
Parameters::Motor Control::Power Loss Ride Thru
REAL
2.0
0.0 to 20.0
%
STOPPED
TECHNICIAN
03821
1648
Pwrl Accel Rate
Parameters::Motor Control::Power Loss Ride Thru
REAL
100
1 to 500
Hz/s
STOPPED
TECHNICIAN
03823
1649
Pwrl Decel Rate
Parameters::Motor Control::Power Loss Ride Thru
REAL
100
1 to 500
Hz/s
STOPPED
TECHNICIAN
03825
1650
Pwrl Time Limit
Parameters::Motor Control::Power Loss Ride Thru
TIME
30.000
0.000 to 300.000
s
STOPPED
TECHNICIAN
03827
1651
Pwrl Active
Parameters::Motor Control::Power Loss Ride Thru
BOOL
NEVER
TECHNICIAN
03829
1658
Current Diff Level
Parameters::Trips::Current Sensor Trip
REAL
25.00
0.00 to 100.00
%
ALWAYS
OPERATOR
4
03843
1659
Modbus TCP Password
Setup::Communications::Base Modbus
Parameters::Base Comms::Modbus
WORD
0000
ALWAYS
TECHNICIAN
03845
1661
PTP Enable
Setup::Communications::PTP
Parameters::Base Comms::PTP
BOOL
FALSE
ALWAYS
TECHNICIAN
03849
1663
Encoder Supply
Setup::Inputs and Outputs::SB Encoder Slot1
Parameters::System Board::SB Encoder Slot 1
USINT
(enum)
0
0:5 V
1:12 V
2:15 V
3:20 V
STOPPED
TECHNICIAN
4
03853
1664
Encoder Lines
Same as PNO 1663
DINT
2048
1 to 100000
STOPPED
TECHNICIAN
4
03855
1665
Encoder Invert
Same as PNO 1663
BOOL
FALSE
STOPPED
TECHNICIAN
4
03857
1666
Encoder Type
Same as PNO 1663
USINT
(enum)
0
Same as PNO 1514
STOPPED
TECHNICIAN
4
03859
1667
High Input Threshold
Same as PNO 1663
BOOL
FALSE
STOPPED
TECHNICIAN
4
03861
1668
Encoder Speed
Monitor::System Board::SB Encoder Slot 1
Parameters::System Board::SB Encoder Slot 1
REAL
x.
Min to Max
RPM
NEVER
TECHNICIAN
4
03863
1669
Encoder Count Reset
Same as PNO 1663
BOOL
FALSE
ALWAYS
TECHNICIAN
2,4
03865
1670
Encoder Count
Same as PNO 1668
DINT
Min to Max
NEVER
TECHNICIAN
1,4
03867
1671
Encoder Lines
Setup::Inputs and Outputs::SB Encoder Slot2
Parameters::System Board::SB Encoder Slot 2
DINT
2048
1 to 100000
STOPPED
TECHNICIAN
4
03869
1672
Encoder Invert
Same as PNO 1671
BOOL
FALSE
STOPPED
TECHNICIAN
4
03871
1673
Encoder Type
Same as PNO 1671
USINT
(enum)
0
Same as PNO 1514
STOPPED
TECHNICIAN
4
03873
1674
High Input Threshold
Same as PNO 1671
BOOL
FALSE
STOPPED
TECHNICIAN
4
03875
1675
Encoder Speed
Monitor::System Board::SB Encoder Slot 2
Parameters::System Board::SB Encoder Slot 2
REAL
x.
Min to Max
RPM
NEVER
OPERATOR
4
03877
1676
Encoder Count Reset
Same as PNO 1671
BOOL
FALSE
ALWAYS
TECHNICIAN
2,4
03879
1677
Encoder Count
Same as PNO 1675
DINT
Min to Max
NEVER
TECHNICIAN
1,4
03881
1678
Output Enable
Setup::Inputs and Outputs::System Board Option
Parameters::System Board::SB Retransmit
BOOL
FALSE
ALWAYS
ENGINEER
4
03883
1679
Output Source
Same as PNO 1678
USINT
(enum)
0
0:SYSTEM BOARD SLOT 1
1:SYSTEM BOARD SLOT 2
2:SYNTHETIC ENCDR
3:DIGITAL OUTPUTS
4:MAIN SPD FEEDBACK
STOPPED
ENGINEER
4
03885
1680
Output Voltage
Same as PNO 1678
USINT
(enum)
0
Same as PNO 1663
ALWAYS
ENGINEER
4
03887
1681
PTP Log Sync Interval
Same as PNO 1661
SINT
-1
-1 to 0
ALWAYS
ENGINEER
03889
1682
Random Pattern AFE
Parameters::Motor Control::Pattern Generator
BOOL
FALSE
ALWAYS
ENGINEER
4
03891
1683
PTP Clock Mode
Same as PNO 1661
USINT
(enum)
0
0:E2E
ALWAYS
ENGINEER
03893
1684
PTP Clock Type
Same as PNO 1661
USINT
(enum)
0
0:MASTER OR SLAVE
1:SLAVE ONLY
ALWAYS
ENGINEER
03895
1685
PTP Lock Threshold
Same as PNO 1661
REAL
0.5
0.1 to 100.0
us
ALWAYS
ENGINEER
03897
1686
PTP Priority2
Same as PNO 1661
USINT
128
0 to 255
ALWAYS
ENGINEER
03899
1687
PTP Offset
Monitor::Communications::PTP
Parameters::Base Comms::PTP
DINT
Min to Max
ns
NEVER
OPERATOR
03901
1688
PTP Locked
Same as PNO 1687
BOOL
NEVER
OPERATOR
03903
1689
PTP State
Same as PNO 1687
USINT
(enum)
0:NONE
1:INITIALISNG
2:FAULTY
3:DISABLED
4:LISTENING
NEVER
OPERATOR
03905

Table of Contents