C-260 Parameter Reference
AC30 series Variable Speed Drive
5:PRE_MASTER
6:MASTER
7:PASSIVE
8:UNCALIBRATED
9:SLAVE
1690
AFE Close Ext PCR
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS
OPERATOR
4
03907
1691
AFE Ext PCR Closed
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS
OPERATOR
4
03909
1692
AFE PF Angle Demand
Parameters::Regen Control::AFE
REAL
0.00
-90.00 to 90.00
deg
ALWAYS
OPERATOR
4
03911
1693
AFE Current Control
Setup::Regen Control
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS
OPERATOR
4
03913
1694
AFE PLL Kp
Parameters::Regen Control::AFE
REAL
5.48
0.00 to 30.00
ALWAYS
OPERATOR
4
03915
1695
AFE PLL Ti
Parameters::Regen Control::AFE
REAL
0.0318
0.0000 to 3.0000
ALWAYS
OPERATOR
4
03917
1696
Synth Encoder Lines
Same as PNO 1678
DINT
2048
1 to 15000000
ALWAYS
TECHNICIAN
4
03919
1697
AFE VDC Min Level
Parameters::Regen Control::AFE
REAL
400.00
340.00 to 5000.00
ALWAYS
OPERATOR
4
03921
1698
Synth Encoder Speed
Same as PNO 1678
REAL
0
0 to 15000000
RPM
ALWAYS
TECHNICIAN
4
03923
1699
PTP Clock
Same as PNO 1687
DT
1970/01/01 to 2038/01/19
NEVER
OPERATOR
03925
1701
Switchover Enable
Parameters::Motor Control::MRAS
BOOL
FALSE
ALWAYS
ENGINEER
4
03929
1702
Synth Encoder Invert
Same as PNO 1678
BOOL
FALSE
ALWAYS
TECHNICIAN
4
03931
1703
AFE Sync Frequency
Monitor::Regen Control
Parameters::Regen Control::AFE
REAL
x.xx
Min to Max
Hz
NEVER
OPERATOR
3,4
03933
1704
AFE Id Demand
Same as PNO 1693
REAL
0.10
-1.50 to 1.50
ALWAYS
OPERATOR
4
03935
1705
AFE Iq Demand
Same as PNO 1693
REAL
0.00
-1.50 to 1.50
ALWAYS
OPERATOR
4
03937
1706
AFE Max Current
Parameters::Regen Control::AFE
REAL
1.50
0.00 to 1.50
ALWAYS
OPERATOR
4
03939
1707
AFE VDC Kp
Parameters::Regen Control::AFE
REAL
8.27
0.00 to 300.00
ALWAYS
OPERATOR
4
03941
1708
AFE VDC Ti
Parameters::Regen Control::AFE
REAL
0.0319
0.0000 to 3.0000
ALWAYS
OPERATOR
4
03943
1709
AFE VDC Ramp
Parameters::Regen Control::AFE
REAL
0.05
0.01 to 100.00
%
ALWAYS
OPERATOR
4
03945
1710
AFE VDC Feed Forward
Parameters::Regen Control::AFE
REAL
0.0000
-1.5000 to 1.5000
ALWAYS
OPERATOR
4
03947
1711
AFE VDC Demand
Same as PNO 1693
REAL
720
340 to 820
V
ALWAYS
OPERATOR
4
03949
1712
AFE Synchronizing
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3,4
03951
1713
AFE Synchronized
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3,4
03953
1714
AFE Enable Drive
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3,4
03955
1715
AFE Phase Loss
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3,4
03957
1716
AFE Brake Mode
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS
OPERATOR
4
03959
1717
AFE Correction Angle
Parameters::Regen Control::AFE
REAL
0.00
-90.00 to 90.00
ALWAYS
OPERATOR
4
03961
1718
AFE Sync Angle
Parameters::Regen Control::AFE
REAL
x.xx
Min to Max
deg
NEVER
OPERATOR
3,4
03963
1721
AFE Status
Same as PNO 1703
USINT
(enum)
0:INACTIVE
1:SYNCHRONIZING
2:SYCHRONIZED
3:SUPPLY FREQ HIGH
4:SUPPLY FREQ LOW
5:SYNC FAILED
NEVER
OPERATOR
3,4
03969
1722
SB Digital Input 2
Monitor::Inputs and Outputs
Parameters::System Board::SB Digital IO
BOOL
NEVER
OPERATOR
4
03971
1723
SB Digital Input 3
Same as PNO 1722
BOOL
NEVER
OPERATOR
4
03973
1725
Peer to Peer Enable
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
BOOL
FALSE
ALWAYS
TECHNICIAN
03977
1726
Destination IP Address
Same as PNO 1725
DWORD
(IP addr)
255.255.255.255
ALWAYS
ENGINEER
03979
1727
Destination Port
Same as PNO 1725
UINT
1250
1 to 65535
ALWAYS
ENGINEER
03981
1728
Local Port
Same as PNO 1725
UINT
1250
1 to 65535
ALWAYS
ENGINEER
03983
1729
Peer to Peer State
Monitor::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
USINT
(enum)
0:DISABLED
1:ACTIVE
2:ERROR
NEVER
OPERATOR
03985
1730
AFE Inductance
Setup::Regen Control
Parameters::Regen Control::AFE
REAL
0.00
0.00 to 1000.00
mH
ALWAYS
OPERATOR
4
03987
1731
AFE Transf Angle Offset
Parameters::Regen Control::AFE
REAL
0.00
0.00 to 360.00
deg
ALWAYS
OPERATOR
4
03989
1732
Motor Start Count
Parameters::Device Manager::Runtime Statistics
UDINT
0 to Max
NEVER
TECHNICIAN
1
03991
1733
Time Since Power-On
Parameters::Device Manager::Runtime Statistics
TIME
0.000 to Max
s
NEVER
TECHNICIAN
03993
1734
AR Trip Mask B
Parameters::Motor Control::Auto Restart
DWORD
00000000
ALWAYS
TECHNICIAN
03995
1735
AR Trip Mask 2 B
Parameters::Motor Control::Auto Restart
DWORD
00000000
ALWAYS
TECHNICIAN
03997
1736
AR Initial Delay B
Parameters::Motor Control::Auto Restart
TIME
60.000
0.000 to 3600.000
s
ALWAYS
OPERATOR
03999
1737
AR Repeat Delay B
Parameters::Motor Control::Auto Restart
TIME
120.000
0.000 to 3600.000
s
ALWAYS
OPERATOR
04001
1738
Enable Auto Save
Parameters::Device Manager::Setup Wizard
BOOL
TRUE
ALWAYS
ENGINEER
04003
1739
System Board Required
Setup::Inputs and Outputs::System Board Option
Parameters::System Board::System Board Option
USINT
(enum)
0
0:NONE
1:DUAL ENCODER
2:ABSOLUTE
CONFIG
TECHNICIAN
04005
1740
System Board Fitted
Parameters::System Board::System Board Option
USINT
(enum)
Same as PNO 1739
NEVER
OPERATOR
1
04007

Table of Contents