280 •
••
• ASCII Flex Protocol QUICKDESIGNER
Explanation: (Compiler Error ) The length was less than 5 when it should have been at least 5.
Error #: 02:90
Error Msg ERROR 02:90 The length for the Rx Long in a Send Command was invalid
Explanation (Compiler Error ) The length was not equal to 4.
Error #: 02:91
Error Msg ERROR 02:91 The length for the Rx Float in a Send Command was invalid
Explanation: (Compiler Error ) The length was less then 4.
Error #: 02:92
Error Msg ERROR 02:92 The Received Literal String did not match
Explanation: A string was received by the Quick Panel, but it did not match the literal string defined by
the user.
Error #: 02:93
Error Msg ERROR 02:93 Length of Literal String in the Rcv Cmd is > 120 Bytes
Explanation: A receive command was being executed but the literal string received was greater than
120 characters.
Error #: 02:94
Error Msg ERROR 02:94 Invalid Type while processing a Receive Command
Explanation: (Compiler Error ) A Receive Command in a Sequence was being executed and an
Invalid type was read, that the Quick Panel did not recognize.
Error #: 02:95
Error Msg ERROR 02:95 The Received Byte Literal did not match
Explanation: A Byte literal(s) was received by the Quick Panel, but it did not match the Byte Literal(s)
defined by the user.
Error #: 02:96
Error Msg ERROR 02:96 Length of Byte Literal in the Rcv Cmd is longer than 120 Bytes
Explanation: A receive command was being executed but the Byte literal(s) received was greater than
120 characters.
Error #: 02:97
Error Msg ERROR 02:97 Length for the Rx string in a Rcv Cmd was invalid
Explanation: (Compiler Error ) The length should have been 5.
Error #: 02:98
Error Msg ERROR 02:98 The length for the Rx Long in a Receive Command was invalid
Explanation: (Compiler Error ) The length was not equal to 4.
Error #: 02:99
Error Msg ERROR 02:99 No digits were found for the Rx Long in a Receive Command
Explanation: A Receive Command was being executed, it was expecting numeric data from the
controller but data was not numeric.
Error #: 02:9A
Error Msg ERROR 02:9A The length for the Rx Float in a Receive Command was invalid