Built-in I/O Specifications - Inputs
Inputs per Module
8
Operating Voltage Range
100β120 VAC
Input Voltage Range
80β144 VAC
AC Frequency
47β63 Hz
Input Current
8.5 mA @ 100VAC at 50Hz
10mA @ 100VAC at 60Hz
Maximum Input Current
16mA @ 144VAC
Input Impedance
15kq @ 50Hz
12kq @ 60Hz
ON Voltage Level
> 60VAC
OFF Voltage Level
< 20VAC
Minimum ON Current
5mA
Maximum OFF Current
2mA
OFF to ON Response
< 40ms
ON to OFF Response
< 40ms
Status Indicators
Logic Side (8 points, green LED)
Commons
2 (4 points/common) Isolated
General Specifications
Current Consumption at 24VDC
140mA
Terminal Block Replacement Part No.
C0-16TB
Weight
5.6 oz (160g)
C0-11ARE-D β 8 AC Input/6 Relay Output Micro PLC
RS-485
+
_
LG
C0-11ARE-D
C1
X1
X2
X3
X4
C2
X5
X6
X7
X8
C3
Y1
Y2
Y3
Y4
C4
Y5
Y6
LNK/ACT
PORT1
PWR
RUN
ERR
RUN
STOP
PORT2
PORT3
RS-232
TX2
RX2
100MBIT
ETHER
NET
TX3
RX3
100 - 120VAC
6 - 240VAC
L
6-27VDC
L
L
L
L
L
6 - 240VAC
6-27VDC
Y
RE-
-11
RT
X
X
-
T
R
3
NK
A
RT1
R
0
Surrounding Air Te mperature (Β°C/Β°F)
32
10
50
20
68
30
85
40
104
50
122
55 Β°C
131 Β°F
2
4
6
8
Points
C0-11ARE-D Temperature Derating Chart
0
45
113
Inputs
* Use every other input.
*
INPUT
COM
100-120 VAC
Internal Module Circuitry
Optical Isolator
Equivalent Input Circuit
INPUT
COM
100-120 VAC
Optical Isolator
X1-X4
Typical
X5-X8
Typical
C1
C2
To X6-X8
commons
To X2-X4
commons
Wiring Diagram
NOTE: When using Ethernet Standard
PLCs, you must use CLICK programming
software version V2.00 or later.
CLICK PLC Hardware User Manual, 6th Edition, Rev. G β C0-USER-M
2β74
Chapter 2: Speciο¬cations