Input Specifications
Inputs per Module
4
Input Range
0–10 V
Resolution
13-bit, 1.22 mV per count
Input Type
Single ended (one common)
Maximum Continuous Overload
Β±100VDC
Input Impedance
>150kΞ©
Filter Characteristics
Low pass, -3 dB at 500Hz
Sample Duration Time
6.25 ms
All Channel Update Rate
25ms
Open Circuit Detection Time
Zero reading within 100 ms
Accuracy vs. Temperature
Β±75 PPM/Β°C maximum
Maximum Inaccuracy
0.5% of range (including
temperature changes)
Linearity Error (End to End)
Β±3 count maximum,
monotonic with no missing
codes
Input Stability and Repeatability
Β±2 count maximum
Full Scale Calibration Error
(Including Offset)
Β±8 count maximum
Offset Calibration Error
Β±8 count maximum
Maximum Crosstalk at DC,
50/60 Hz
Β±2 count maximum
Field to Logic Side Isolation
1800VAC for 1 sec.
External 24VDC Power
Required
65mA
Base Power Required (24VDC)
23mA
Terminal Block Replacement
AutomationDirect p/n C0-8TB
Weight
2.9 oz (82g)
C0-04AD-2 – 4-Channel Analog Voltage Input Module
4-channel analog voltage input module, 13-bit resolution, range: 0–10V. External 24VDC
power required, removable terminal block included.
CH1
CH2
CH3
CH4
0V
0V
0V
0V
0V
24V
0V
C0-04AD-2
0-10V
INPUT
All β€˜0V’
terminals are
connected
internally.
C
H1
C
H2
C
H3
C
H
4
0
V
0V
0
V
0
V
0V
24V
0
V
C0-04AD-2
0
-
10
V
I
NP
U
T
A
t
e
co
in
+
–
Voltage
Transmitter
+
–
Voltage
Transmitter
+
–
Voltage
Transmitter
+
–
Voltage
Transmitter
+
–
24VDC
Power
Supply
CHn
0V
Connect the unused
channel to 0V terminal.
Wiring Diagram
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
ZL-RTB20 20-pin feed-
through connector module
11-pin connector cable
ZL-C0-CBL11 (0.5 m length)
ZL-C0-CBL11-1 (1.0 m length)
ZL-C0-CBL11-2 (2.0 m length)
NOTE: When using this module you must
also use CLICK programming software and
PLC firmware version V1.40 or later.
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–137
Chapter 2: Specifications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect CLICK Series and is the answer not in the manual?

AutomationDirect CLICK Series Specifications

General IconGeneral
BrandAutomationDirect
ModelCLICK Series
CategoryController
LanguageEnglish

Related product manuals