Typical Relay Life (Operations)
at Room Temperature
Voltage & Load Type Relay Life
30VDC, 1A Resistive 300,000 cycles
30VDC, 1A Solenoid 50,000 cycles
250VAC, 1A Resistive 500,000 cycles
250VAC, 1A Solenoid 200,000 cycles
ON to OFF = 1 cycle
C0-08TR β 8-Point Relay Output Module
8-point 6β240 VAC /6β27 VDC relay output module, 8 Form A (SPST) relays, 2 commons,
isolated, 4 A/common, removable terminal block included.
OUTPUT
COM
6-27 VDC
L
Internal Module Circuitry
Equivalent Output Circuit
6-240
VAC
* Varistor Joule Rating: 20 J
*
0
Surrounding Air Te mperature (Β°C/Β°F)
32
10
50
20
68
30
85
40
104
50
122
55 Β°C
131 Β°F
2
4
6
8
Points
Output Temperature Derating Chart
0
* Use every other output.
*
C0-08TR
250V 1A 50-60Hz
30V 1A
PWR
γξ
OUTPUT
-
A
TP
T
L
L
L
L
L
L
L
L
6 - 27VDC
6 - 240VAC
6 - 27VDC
6 - 240VAC
N.C.
N.C. = Not Connected
C2
7
3
2
5
4
8
6
1
C1
ZIPLink Pre-Wired
PLC Connection
Cables and Modules
for CLICK PLC
11-pin connector cable
ZL-C0-CBL11 (0.5 m length)
ZL-C0-CBL11-1 (1.0 m length)
ZL-C0-CBL11-2 (2.0 m length)
Wiring Diagram
ZL-RTB20
20-pin feed-through
connector module
Output Specifications
Outputs per Module
8
Operating Voltage Range
6β27 VDC / 6β240 VAC
Output Voltage Range
5β30 VDC / 5β264 VAC
Output Type
Relay, form A (SPST)
AC Frequency
47β63 Hz
Maximum Current (resistive)
1A /point, 4A /common
Minimum Load Current
5mA @ 5VDC
Maximum Leakage Current
0.1 mA @ 264VAC
Maximum Inrush Current
3A for 10ms
OFF to ON Response
< 15ms
ON to OFF Response
< 15ms
Status Indicators
Logic Side (8 points, red LED)
Power Indicator (green LED)
Commons
2 (4 points/common) Isolated
Bus Power Required (24VDC)
Max. 100mA (All Outputs On)
Protection Circuit
Not built into the module - Install protection
elements such as external fuse.
Terminal Block Replacement
AutomationDirect p/n C0-8TB
Weight
3.9 oz (110g)
CLICK PLC Hardware User Manual, 6th Edition, Rev. G β C0-USER-M
2β128
Chapter 2: Speciο¬cations