EasyManuals Logo

AutomationDirect CLICK Series User Manual

AutomationDirect CLICK Series
301 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #227 background imageLoading...
Page #227 background image
PLC’s Integrated Transient Suppressors
Although the PLC’s outputs typically have integrated suppressors to protect against transients,
they are not capable of handling them all. It is usually necessary to have some additional
transient suppression for an inductive load.
Here is another example using the same 24V, 125mA, 3W relay used earlier. This example
measures the PNP transistor output of a D0-06DD2 PLC, which incorporates an integrated
Zener diode for transient suppression. Instead of the 140V peak in the first example, the
transient voltage here is limited to about 40V by the Zener diode. While the PLC will probably
tolerate repeated transients in this range for some time, the 40V is still beyond the module’s
peak output voltage rating of 30V.
5HOD\οΏ½
&RLOοΏ½
οΏ½οΏ½
9'&
2VFLOORVFRSH
οΏ½οΏ½)RUοΏ½WKLVοΏ½H[DPSOHοΏ½οΏ½DοΏ½οΏ½οΏ½9οΏ½οΏ½οΏ½οΏ½P$οΏ½οΏ½:οΏ½
UHOD\οΏ½LVοΏ½XVHGοΏ½οΏ½$XWRPDWLRQ'LUHFWοΏ½
SDUWοΏ½QRοΏ½οΏ½οΏ½οΏ½οΏ½οΏ½οΏ½&οΏ½οΏ½οΏ½'οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½
οΏ½οΏ½
9ROWV
οΏ½οΏ½
οΏ½οΏ½
οΏ½
Example: Small Inductive Load with Only Integrated Suppression
The next example uses the same circuit as above, but with a larger 24V, 290mA, 7W relay
thereby creating a larger inductive load. As you can see, the transient voltage generated is much
worse, peaking at over 50V. Driving an inductive load of this size without additional transient
suppression is very likely to permanently damage the PLC output.
Example: Larger Inductive Load with Only Integrated Suppression
5HOD\οΏ½
&RLOοΏ½
οΏ½οΏ½
9'&
2VFLOORVFRSH
οΏ½οΏ½)RUοΏ½WKLVοΏ½H[DPSOHοΏ½οΏ½DοΏ½οΏ½οΏ½οΏ½οΏ½οΏ½οΏ½P$οΏ½οΏ½:οΏ½
UHOD\οΏ½LVοΏ½XVHGοΏ½οΏ½$XWRPDWLRQ'LUHFWοΏ½
SDUWοΏ½QRοΏ½οΏ½6&οΏ½(οΏ½οΏ½*οΏ½οΏ½οΏ½9'&οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½οΏ½
οΏ½
οΏ½οΏ½οΏ½
9ROWV
Additional transient suppression should be used in both these examples. If you are unable
to measure the transients generated by the connected loads of your control system, using
additional transient suppression on all inductive loads would be the safest practice.
CLICK PLC Hardware User Manual, 5th Edition, Rev. F – C0-USER-M
3–34
Chapter 3: Installation and Wiring

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect CLICK Series and is the answer not in the manual?

AutomationDirect CLICK Series Specifications

General IconGeneral
BrandAutomationDirect
ModelCLICK Series
CategoryController
LanguageEnglish

Related product manuals