EasyManuals Logo

AutomationDirect CLICK Series User Manual

AutomationDirect CLICK Series
301 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #257 background imageLoading...
Page #257 background image
Case 2: Connect Com Port 1 to other devices that support the Modbus TCP
(client/server) protocol via a switch or hub.
NOTE: Com Port 1 can communicate with any number of servers (slaves) using the Receive and/or Send
instructions. However, Com Port 1 can communicate with up to 4 servers at the same time. If the ladder
program has sent a message to 4 different servers and tries to send a message to another server, the
CLICK PLC unit disconnects the first server and establishes a connection with the new server, maintaining
a total of 4 servers.
NOTE: Com Port 1 can communicate with up to 3 clients (masters). If a client attempts to establish
communication with Com Port 1 while it is communicating with 3 clients, the CLICK PLC unit replies with
an error to the forth client.
CLICK PLC Hardware User Manual, 6th Edition, Rev. F – C0-USER-M
4–18
Chapter 4: PLC Communications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect CLICK Series and is the answer not in the manual?

AutomationDirect CLICK Series Specifications

General IconGeneral
BrandAutomationDirect
ModelCLICK Series
CategoryController
LanguageEnglish

Related product manuals