6-4 BE1-951 Reporting and Alarm Functions 9328900990 Rev L
General Status Report
A General Status Report is available through the communication ports using the RG-STAT command.
This report lists all of the information required to determine the status of the relay. An example of a typical
general status report follows. In the explanation of what each line represents, cross-references are made
to the corresponding HMI screens that contain that data.
>RG-STAT
INPUT(1234) STATUS : 0000
OUTPUT(A12345) STATUS : 000000
CO-OUT(A12345) STATUS : LLLLLL
CO-43/143/243/343 STATUS : 0000
CO-101(101SC) STATUS : AFTER CLOSE(1)
CO-GROUP STATUS : L
ACTIVE LOGIC STATUS : BASIC-OC
RECLOSER(79) STATUS : OFF
LOGIC VAR(00-31) STATUS : 00000000 00000000 00000000 00000000
LOGIC VAR(32-63) STATUS : 00000000 00000000 00000000 00100010
LOGIC VAR(64-95) STATUS : 01000000 00000000 00000000 00000000
ACTIVE GROUP STATUS : 0
BREAKER(52) STATUS : CLOSED
DIAG/ALARM STATUS : 0 RELAY, 0 LOGIC, 0 MAJOR, 0 MINOR
Input (1234)
This line reports the status of contact sensing inputs IN1, IN2, IN3, and IN4. Input information is available
at HMI Screen 1.5.1. 0 indicates a de-energized input and 1 indicates an energized input. See Section 3,
Input and Output Functions, for more information about contact sensing input operation.
Output (A12345)
Current output contact status is reported on this line. This information is also available at HMI Screen
1.5.2. 0 indicates a de-energized output and 1 indicates an energized output. More information about
output contact operation is available in Section 3, Input and Output Functions.
CO-OUT (A12345)
This line reports the logic override of the output contacts. Logic override status is reported at HMI Screen
1.5.3. Section 3, Input and Output Functions, provides more information about overriding output contacts.
CO-43/143/243/343
Virtual switch function status is reported on this line. This information is also available at HMI Screen
1.5.4. See Section 4, Protection and Control, for more information about virtual switch operation.
CO-101 (101SC)
This line reports the status of the virtual breaker control switch slip-contact output. More information about
the virtual breaker control switch is available in Section 4, Protection and Control, Virtual Switches.
CO-Group
The logic override status of the setting group selection function is reported on this line. For more
information about this function, refer to Section 4, Protection and Control, Settings Groups.
Active Logic
This line reports the name of the active logic scheme. The active logic scheme name can be viewed at
HMI Screen 5 and with the SL-N command. See Section 7, BESTlogic Programmable Logic, Logic
Scheme Names, for more information about this function.
Recloser (79)
The status of the recloser is reported on this line. HMI Screen 1.1 also reports this information. More
information about the recloser function is available in Section 4, Protection and Control.
Logic Var (00-31), Logic Var (32-63), and Logic (64-95)
These two lines report the status of each BESTlogic variable. These lines can be entered into
Table 6-3
to determine the status of each logic variable. Section 7, BESTlogic Programmable Logic, provides more
information about BESTlogic variables.